Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2005 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1) SOIL WATER TEST IS OK. 2) OVERHEAD WATER DISTRIBUTION IS OK. 2) OVERHEAD WATER DISTRIBUTION IS OK. 3) R.W.C WATER TEST IS OK. | |
| 06/06/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MAX FIXTURE UNIT LOAD FOR 2" VTR IS 24 F.U. SHALL PROVIDE MIN OF 3" VTR. 2) RETEST THE SYSTEM. |