Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 03/28/2005 |
PLUMBING - YARD WTR LINE/TEST |
|
Approved |
IVRS - Inspection :* |
| 03/25/2005 |
PLUMBING - YARD WTR LINE/TEST |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 01/04/2005 |
PLUMBING - YARD WTR LINE/TEST |
|
Not ready for Inspection |
IVRS - Inspection :*PLEASE EXPOSE ALL JOINTS FOR INSP. PLEASE SEE SPCE 15010-7 SEC 3104. FOR INSTALLATION STANDARDS FOR INSTALLATION & PROPER BACK ?? REMOVE ALL ROCK & NO BRIDGING INSTALLED ON FIRM BED. PLEASE NOTE DEPTH AT FOOTING |
| 12/29/2004 |
PLUMBING - YARD WTR LINE/TEST |
|
Partial Approval |
IVRS - Inspection :*/1 1/2" PVC SCH 40 FROM BUILDING SERVICE VALVE BACK APP. 70' TO JUST BEFORE 2X3X1 1/2 TEE 65 PSI AIR TEST OK WILL NEED TO SEE FINAL CONNECTION AT COUPLING WITH TEST ON MAIN. |
| 12/07/2004 |
PLUMBING - YARD WTR LINE/TEST |
|
Not ready for Inspection |
IVRS - Inspection :*/TEST ON INSIDE ONLY |
| 08/30/2004 |
PLUMBING - YARD WTR LINE/TEST |
|
Partial Approval |
IVRS - Inspection :*/PA-STUB ONLY |