Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/27/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 102803AM |
| 10/24/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) INSIDE MAIN DISCONNECT INSTALL GREEN SCREW WHICH CONNECT ISOLATED GROUND BAR TO ENCLOSURE 2) INSIDE MAIN DISCONNECT-INSTALL REJECT PINS SO ONLY CLASS RK FUSES CAN BE USED 3) COVER BACK SUPPORT HOLE, SO WATER WILL NOT GET INTO TERMINALS 4) INSTALL PANEL LOWER ON PANEL A CORRECTLY AND LABEL USED BREAKERS PER SCHEDULE 5) PLAN NOTES ON E-3 STATE A 100 W METAL HALIDE TO BE USED, SEE PLAN. J-BOX AT BASE OF SOUTH LIGTH NOT TO BE COVERED |
| 10/14/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK CABLE DROP 2) OK TO CLEAR SERVICE FOR CELL SITE |