Permit: T03CM03402

Parcel: 13342001C

Inspection Status: Approved

Inspection History: ENGINEERING - FINAL

Date Description Inspector Results Comments
03/16/2006 ENGINEERING - FINAL Approved APPROVED PER ERNIE DUARTE.
10/11/2005 ENGINEERING - FINAL Cancelled CANCELED BY CONTRACTOR, TCO APPROVED ON 10-10-05
10/10/2005 ENGINEERING - FINAL Partial Approval TEMPORARY C OF O APPROVED.
1. PROVIDE VERTICAL CURB AT END OF SIDEWALK AT HANDICAP RAMPS TO CONTROL DRAINAGE ACROSS RAMPS.
2. COMPLETE CURBING AT PARKING AREAS WHERE NEEDED.
3. PROVIDE WATER HARVEST AREAS AND POSITIVE DRAINAGE TO SIDEWALK SCUPPERS.
4. PERMANENT C OF O NOT TO BE GIVEN UNTIL THE RETENTION/DETENTION BASIN FUNCTIONS PROPERLY AND THE ARIZONA REGISTERED ENGINEER PROVIDES A LETTER CERTIFIYING CONSTRUCTION AND OPERABILITY.
10/07/2005 ENGINEERING - FINAL Denied 1. COMPLETE ALL SITE WORK INCLUDING OVERHEAD WORK ON COVERED PARKING.
2. PROVIDE 6" MAX WATER HAZARD AREA WITH RELEASE POINT AT THE SIDEWALK SCUPPERS.
3. COMPLETE ALL CURBS AND PAVEMENT.
4. REMOVE ALL CONSTRUCTION MATERIAL AND DEBRIS INCLUDING TEMPORARY FENCING.
5. PERMANENT C OF O NOT TO BE GIVEN UNTIL THE RETENTION/DETENTION BASIN FUNCTIONS PROPERLY AND THE ARIZONA REGISTERED ENGINEER PROVIDES A LETTER CERTIFIYING CONSTRUCTION AND OPERABILITY.