Permit: T03CM03394

Parcel: 13342001C

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
03/31/2005 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*OK ROUGH
03/29/2005 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :* 1) LETTER TO BE FROM MANUFACTURE OF BOXES AS TO REMEDY FOR BROKEN CABLE CLAMPS AS DISCUSSED WITH MARTIN OF CASCADE ELECTRIC
03/25/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/24/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :* NOTE BOXES AT STUCCO MAY NEED EXTENDER RINGS. 1) TIGHTEN CABLE CLAMPS 4/0 BOXES. 2) BROKEN BOX NEED REPLACEMENT. 3) MANUFACTURE TO SUPPLY INSERTS FOR BOXES.
02/14/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :* 1) MOVE VDV CABLES FROM SHARP METAL EDGES AT TRUSSES. OK PRE LID