Permit: T03CM03390

Parcel: 137340010


Addresses:

1650 W VALENCIA RD


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T03CM03390

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/04/2004 PLUMBING - FINAL Approved 1) GAS PRESSURE TEST IS OK. 2) GAS SHUT OFF VALVE IS OK. 3) REGULATOR HAS BEEN TAGGED.
03/02/2004 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) MUST PROVIDE AIR TEST 60 LB MIN. ON GAS SYSTEM. 2) MUST PERMANENTLY TAG REGULATOR STATING " WARNING ½" TO 5 PSI DO NOT REMOVE" SEE SEC. 1218.4 SUB NOTE #4 94 UPC. 3) GAS LINE HAS BEEN PAINTED. CAN NOT VERIFY MARKINGS ON PIPE.