Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 01/21/2004 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 11/17/2003 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) CANCELLED |
| 10/16/2003 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) DOES NOT INCLUDE STEPS |
| 10/13/2003 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) STEPS AT EXTERIOR NOT INSTALLED AND LANDING 2) 8" MAXIMUM NAIL SPACING ON WALLS (12" WITH SCREWS) 3) 3/8" MINIMUM NAILING AT EDGES (FROM EDGES) 4) CEILING REQUIRES SAG RESISTANT DRYWALL 5) NAIL ALL IN WATER HEATER CLOSET 6) REMOVE WIRING AND J-BOXES IN WALL TO EXISTING OR BRING THEM TO THE SURFACE |
| 10/03/2003 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) DOES NOT INCLUDE STEPS, OPENING INTO MAIN STRUCTURE AND J-BOXES TO BE REMOVED IN EXISTING WALL |
| 10/01/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE WATER TEST OF ALL DRAIN WASTE AND VENT PLUMBING TO ROOF 2) BLOCK HEATING BOOTS ON 3 SIDES 3) PROVIDE A 10 PSI GAS PRESSURE TEST 4) BOND GAS LINE 5) NO PLANS ON SITE, STOPPED INSPECTION |
| 09/19/2003 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |