Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03CM03384

Parcel: 129063170


Addresses:

2837 E 21ST ST

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
09/09/2003 BUILDING - FINAL Approved IVRS - Inspection 0000*
07/18/2003 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) 01005 AND 01015 POURED WITHOUT INSPECTION DIG DOWN TO EXPOSE DEPTH OF FOOTING AT EACH CORNER 2) INSTALL ANCHOR BOLTS WITHIN 12" EACH END BOTTOM PLATES (WOOD) 3) CANNOT HAVE ELECTRIC ROMEX EXPOSED GAUGE 4) OUTLETS TO BE GFCI PROTECTED 5) CROSS BRACE TRUSSES BOTH ENDS OF RUN 6) NEED COPY OF TRUSS DRAWINGS FROM MANUFACTURER 7) UNCOVER ELECTRIC FROM MAIN PANEL TO GARAGE 8) LABEL CIRCUITS SERVED MAIN PANEL AT HOUSE AND GARAGE SUB-PANEL 9) REPLACE CUT OUT BEARING STUD AT COOLER LOCATION 10) HAVE EVAPORATIVE COOLER ADDED TO PLAN AND INSTALL APPROVED ELECTRIC DISCONNECT 11) SEPARATE NEUTRAL WIRES FROM GROUND WIRES ONTO SEPARATE BUS BAR 12) PROVIDE SEPARATE GROUND AT GARAGE (DRIVE 2 GROUND RODS AND CONNECT INTO GARAGE SUB-PANEL 13) MINIMUM CLEARANCE 6" EXTERIOR WOOD TRIM AND SIDING TO DIRT