Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T03CM03383
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/17/2003 | FRAMING | Approved | IVRS - Inspection 0000* | |
11/14/2003 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) GAS TEST FAILED 2) DWV TEST FAILED 3) EXTEND GAS BOND WIRE TO GAS STUB 4) FRAMING WITHELD FOR OTHER INTERMEDIATE |