Permit: T03CM03375

Parcel: 125100670


Addresses:

3761 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T03CM03375

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
01/24/2005 ELECTRIC - ABOVE CEILING Approved
01/06/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*/1)IF SUPPORT WIRES USED THEY MUST BE ATTACHED AT BOTH ENDS 300.11 2)APPROVED EXTENDER RUGS NEEDED FOR BOXES MORE THAN 1/4" FROM BOX TO SURFACE 370-20/314.2 NON-COMBUSTABLE FLUSH AT WOOD (COMBUSTABLE) 3)WALL LIGHTS-BOXES FOR FILL OF CONDUCTORS & FILL UNUSED OPENINGS. 4)OUTSIDE LIGHTING TO CONFORM WITH TUCSON LIGHTING CODES. 5)NEON POWER PRO TO BE PROPERLY SUPPORTED - RESTROOM ALSO VERIFY IF ALLISON TRANSFORMER IS DIMMABLE
12/01/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*/ 1) KITCHEN AND ADJOINING ROOMS
11/29/2004 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The fixtures are not per plans and specifications.| 250*
1) CEILING GRID IN KITCHEN AND ADJACENT AREAS IS INCOMPLETE AND DROP IN FIXTURES ARE MISSING SEISMIC AND GRID SUPPORTS
11/24/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :* ROOM 11S PANTRY & ROOM 111 - LAY-IN FIXTURES.
11/12/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*/ 1) HARD CEILING IN MAIN DINIG HALL
10/27/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*/OK LOWER CEILINGS DINNING ROOM 1)SUPPORT M/C CABLES WITHIN 12" OF BOX 2)FINISH GROUNDING OF BOXES
10/18/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*/ 1) FLOWING AREAS OK TO LOUVER 2) MAIN ENTRY INSIDE AND OUTSIDE 3) ROTISSERIE AREA 4) BAR AND DINING AREA 5) SERVICE AREA #2 6) BAKERY
09/10/2004 ELECTRIC - ABOVE CEILING Partial Approval PARTIAL