Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/25/2004 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK FOR FINAL C OF O |
| 02/24/2004 |
MECHANICAL - FINAL |
|
Denied |