Permit: T03CM03352


Addresses:

3124 N SWAN RD

Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Date Description Inspector Results Comments
02/12/2004 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection 0000*
02/10/2004 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection 0000*/ 1) MAINTAIN A SAFE WORKING SPACE IN FRONT OF SERVICE EQUIPMENT 2) WE HAVE A DRAIN SPOUT ABOVE SERVICE THAT NEED TO BE MOVED 3) BONDING JUMPER TO BE SIZED PER 250.102 AND 250.66 4) A BONDING DEVICE IS NEED ON INSIDE NIPPLE IN CT CAN 5) FINISH INTERIOR AS DISCUSSED