Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 02/12/2004 |
ELECTRIC - TEMP POWER FOR TEST |
|
Approved |
IVRS - Inspection 0000* |
| 02/10/2004 |
ELECTRIC - TEMP POWER FOR TEST |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) MAINTAIN A SAFE WORKING SPACE IN FRONT OF SERVICE EQUIPMENT 2) WE HAVE A DRAIN SPOUT ABOVE SERVICE THAT NEED TO BE MOVED 3) BONDING JUMPER TO BE SIZED PER 250.102 AND 250.66 4) A BONDING DEVICE IS NEED ON INSIDE NIPPLE IN CT CAN 5) FINISH INTERIOR AS DISCUSSED |