Permit: T03CM03350

Parcel: 11627504A

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
08/20/2003 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*/1) WASTE AND VENT SYSTEM IS OK. 2) WATER DISTRIBUTION IS OK. 3) OK FOR DRYWALL.
08/14/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/1) SOIL WATER TEST IS OK. 2) P.O.C. OF NEW BLDG DRAIN TO EXISTING BLDG DRAIN IS OK. 3) OK TO BACKFILL TRENCH.
08/13/2003 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*/1) MUST USE SPECIALTY COUPLINGS WHEN CONNECTING ABS TO CAST IRON @ FLOOR DRAINS. 2)MUST PROVIDE BLIND PLUG AS PERM CAP FOR EXISTING DRINKING FOUNTAIN. 3) RE TEST SYSTEM.
08/12/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) NOTES: #1,2 AND 4 ARE OK. 2) OK TO DRYWALL. 3) CAN NOT USE A SAN CROSS FOR DRAINAGE UNLESS THE BARREL IS (2) PIPE SIZE LARGER THAN TRAP ARMS. 4) RE-TEST SYSTEM.
08/08/2003 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) TRAP MUST BE THE SAME SIZE AS TRAP ARM TO WHICH IT'S CONNECTED SEE SECTION: 1003.3 94 UPC TRAP ARM FOR SHOWER IS 2" THEN CONNECTS TO 3" EXISTING 2) LAVATORY TRAP ARM IS 2" YOU CAN ONLY BE (1) PIPE SIZE LARGER THAN OUTLET OF FIXTURE. THAT MEANS MAY TRAP SIZE IS 1 1/2 FOR LAVATORY THEN TRAP ARM MUST BE 1 1/2" 1003.3 94 UPC 3) CAN NOT FLAT VENT FLOOR DRAINS BECAUSE THERE IS NO STRUCTURAL CONDITION SEE SECTION 905.3 94 UPC 4) H.C. WATER CLOSET FLUSH VALVE HANDLES MUST BE ON OPEN SIDE OF STALL (ADA) SPECS