Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 09/08/2003 |
MECHANICAL - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000*/ ALL CORRECTIONS HAVE BEEN MADE. OK FOR CEILING TILES. LEAVE OUT A TILE UNDER EACH FAN COIL, NEED TO SEE FAN COILS LABELED WITH SAME NUMBER AS CONDENSING UNIT. WILL CHECK ON FINAL. |
| 09/03/2003 |
MECHANICAL - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE TRAPS ON CONDENSATE DRAIN LINES. TERMINATE SECONDARY IN A CONSPCICUOUS LOCATION. 2) STRAP FLEX DUCT UP OFF OF GRID AND LIGHTS 3) ISOLATE COPPER REFER LINES FROM SCRAPING ON OPENING INTO FAN COIL. RECALL FOR INSPECTION |
| 08/18/2003 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/SUSPENDED ROUGH DUCT ONLY |