Permit: T03CM03337

Parcel: 115062140


Addresses:

1800 N STONE AV #1


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T03CM03337

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
09/08/2003 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*/ ALL CORRECTIONS HAVE BEEN MADE. OK FOR CEILING TILES. LEAVE OUT A TILE UNDER EACH FAN COIL, NEED TO SEE FAN COILS LABELED WITH SAME NUMBER AS CONDENSING UNIT. WILL CHECK ON FINAL.
09/03/2003 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection 0999*/ 1) PROVIDE TRAPS ON CONDENSATE DRAIN LINES. TERMINATE SECONDARY IN A CONSPCICUOUS LOCATION. 2) STRAP FLEX DUCT UP OFF OF GRID AND LIGHTS 3) ISOLATE COPPER REFER LINES FROM SCRAPING ON OPENING INTO FAN COIL. RECALL FOR INSPECTION
08/18/2003 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/SUSPENDED ROUGH DUCT ONLY