Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T03CM03337
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/08/2003 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
09/05/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* ALL DISCONNECTS, UNLESS PERMITED BY THE MANUFACTURER, MUST BE MOUNTED IN THE VERTICAL POSTION. | |
09/03/2003 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0236*/ 1) CABLES MAY NOT BE BUNDLED. THE M.C. CABLE MUST BE UN BUNDLED, SPREAD OUT, AND SUPPORTED EVERY 6 FEET. DO NOT GROUP MORE THAN THREE (3) OR FOUR (4) CABLES. DO NOT USE PLSTIC TIE-RAPS TO SUPPORT CABLES. THE SEISMIC WIRES SHOULD BE SET STRAIGHT NOT AT DIAGONAL ANGLES. THEY SHOULD NOT SWING OR TWIST IF DISLODGED FROM CEILING GRID | |
08/18/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* |