Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/15/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 10/14/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) SEE #3 AND #2 FROM 10/09 |
| 10/10/2003 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) SEE #1, 2 AND 3 FROM PREVIOUS INSPECTION |
| 10/09/2003 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) NAIL PROTECT ABS AT WATER HEATER PLATFORM 2) NAIL PROTECT ALL ELECTRICAL WITHIN 1 1/4" FROM EDGE OF STUD AND NO ROMEX TO TOUCH GUSSET PLATES 3) ROMEX TO EXHAUST FAN IN POWDER ROOM JUST DANGLING 4) NAIL PROTECT PLUMBING 2ND FLOOR 5) SECURE GAS LINE AT FAU 6) BLOCK MECHANICAL PLATFORM 7) NO TEST ON DWV'S SOUTH SIDE OF HOUSE 2ND FLOOR 8) SECURE WATER LINES AT MASTER SHOWER 9) FIRE BLOCK AT 2ND FLOOR BEDROOMS MISSING 10) WATER LINE BEHIND TUB TOUCHING GAS VENT, NEED 6" CLEARANCE |
| 10/07/2003 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) CANCELLED ON SITE BY SUPER 2) LATH NOT INSTALLED |