Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 09/26/2003 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000*/ 1) BLOCK BETWEEN TRUSSES AND NAIL AT 2ND FLOOR |
| 09/25/2003 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) REPLACE OVERNOTCHED STUDS NORTH WALL 2) 2 X 6 WALLS REQUIRE 2 X6 PLATES 3) PROVIDE DETAIL FOR 2 X 6 WALL 1ST AND 2ND FLOOR LAUNDRY ROOM AREA BELOW AND ABOVE 4) PATIO ROOF NOT COMPLETE 5) STOPPED INSPECTION NEXT FAILURE WILL RESULT IN A REFEE |
| 09/24/2003 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) SEE PREVIOUS INSPECTION |
| 09/23/2003 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) OVERSPANS NORTH WALL, WEST WALL FIRST FLOOR 2) SHEAR SOUTH EAST WALL 2ND FLOOR NOT NAILED 3) BRACING NOT PER PLAN 4) CHECK PERIMETER NAILING 5) OVER SPAN 2ND FLOOR NORTH EAST CORNER 6) 2 X 6 WALL UPSTAIRS BATHROOM NORTH NOT ON PLAN REVISE |
| 09/19/2003 |
EXT METAL CLIPS/EXT SHEATHING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) INSPECTION STOPPED BY SUPER |