Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/05/2003 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 08/01/2003 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) NO VENT ON UPSTAIRS LAVATORY 2) NO VENT ON UPSTAIRS SHOWER 3) N/H BAND IS LISTED FOR CAST IRON ONLY-USED APPROVED BAND 4) PLUMBERS TAPE IS NOT APPROVED STRAPPING 5) ISOLATE COPPER TOUCHING COPPER 6) THIS MAY NOT BE A COMPLETE LIST SO CHECK ALL WORK |
| 07/30/2003 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* |