Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T03CM03314

Parcel: 119214300

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/07/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
08/05/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) NORTH WALL REPLACE DAMAGED ROMEX 2) INSTALL CEILING BOX IN LIVING ROOM 3) TAKE OUT ALL BRANCH CIRCUITS OUT AND NAIL