Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/20/2003 |
MECHANICAL - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 11/14/2003 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PROVIDE POSITIVE PITCH AT PRIMARY CONDENSATE LINE |
| 11/10/2003 |
MECHANICAL - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) FIRE BLOCK MISSING AT BALLOON WALL - WEST SIDE. 2) PROVIDE POSITIVE FLOW FOR PRIMARY CONDENSATE LINES. |
| 11/07/2003 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 11/05/2003 |
MECHANICAL - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) NO TEST ON DWVS. 2) PROVIDE AN APPROVED DETAIL FOR STAIR LANDING TO 2ND FLOOR. STOPPED INSPECTION RECALL WHEN READY. |