Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T03CM03292
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/09/2004 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000* | |
04/07/2004 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0245*/ 1) SUPPORT OUTLET BOX FOR GFI RECEPTACLE 2) INSTALL PERMANENT. ADDESS LABEL ON SERVICE, MUST BE SCREWED OR RIVITED. NO MAGIC MARKER 3) USE 1/4" BOLT MINIMUM TO SUPPORT, RISER CONDUIT, DRYWALL SCREW NOT STRONG ENOUGH |