Permit: T03CM03292

Parcel: 116275190

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T03CM03292

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/11/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*/ 1) OK WALLS AND HARD LIDS
06/10/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ NOTES: 1) ROMEX MUST BE 1ΒΌ" MIN. DISTANCE FROM FACE OF METAL STUDS TO PROTECT FROM SCREWS. 2) CABLE RUN IN SLAB MUST BE TYPE UF. NM ROMEX NOT RATED FOR UNDERGROUND USE. 3) ALL SWITCHES NEED TO BE GROUNDING TYPE WITH EQUIP GROUND WIRE ATTACHED.