Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM03292
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/11/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :*/ 1) OK WALLS AND HARD LIDS | |
06/10/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ NOTES: 1) ROMEX MUST BE 1ΒΌ" MIN. DISTANCE FROM FACE OF METAL STUDS TO PROTECT FROM SCREWS. 2) CABLE RUN IN SLAB MUST BE TYPE UF. NM ROMEX NOT RATED FOR UNDERGROUND USE. 3) ALL SWITCHES NEED TO BE GROUNDING TYPE WITH EQUIP GROUND WIRE ATTACHED. |