Permit: T03CM03263

Parcel: 125160860

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
02/03/2005 BUILDING - FINAL Approved IVRS - Inspection :*
02/02/2005 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LABEL ALL CIRCUITS IN ELECTRIC PANEL
2) BATHROOM'S PLUMBING NOT COMPLETE
3) ELECTRIC OUTLETS NOT ALLOWED UNDER BAR COUNTER TOPS GREATER THAN 6"
4) PROVIDE REVISED PLAN FOR RELOCATION OF MASONRY FIREPLACE AND PROVIDE PROOF THAT FOOTING EXISTS UNDER CURRENT FIREPLACE LOCATION
5) FIREPLACE HAS OPENING GREATER THAN 6 SQUARE FEET. REQUIRES 18" HEARTH
6) PENINSULA IN KITCHEN REQUIRES GFCI OUTLET
7) DISHWASHER DRAIN MUST EXTEND TO WITHIN 2" OF KITCHEN SINK FLOOD RIM OR INSTALL AN AIR GAP DEVICE
8) ROOF MOUNTED GAS PACK UNIT ARE NOT INSTALLED AND NO POWER EXISTS WITHIN SEVERAL FEE
9) WATER HEATER COMBUSTION RELIEF NOT INSTALLED-SEE PLAN
10) WET BAR GFCI OUTLET CANNOT BE ON BATHROOOM GFCI CIRCUIT