Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date |
Description |
Inspector |
Results |
Comments |
| 12/16/2004 |
MECHANICAL - HOODS |
|
Approved |
|
| 08/04/2004 |
MECHANICAL - HOODS |
|
Partial Approval |
IVRS - Inspection :*/ 1) RATED CHASE UP INTO CURB, OK |
| 08/03/2004 |
MECHANICAL - HOODS |
|
Partial Approval |
IVRS - Inspection :NEED TO VERIFY THAT DRY WALL CHASE EXTENDS UP INSIDE CURB |
| 07/26/2004 |
MECHANICAL - HOODS |
|
Partial Approval |
IVRS - Inspection :*/ 1) THIS EXHAUST DUCT IS NOT CENTERED IN CHASE 2) THERE HAS BEEN NO CORRECTION 3) APPROVED PLAN SHOWS 6" MINIMUM CLEARANCE TO RIDGID CHASE, 1 HR |
| 07/22/2004 |
MECHANICAL - HOODS |
|
Partial Approval |
IVRS - Inspection :*/ 1) EXHAUST DUCT 16 GA. BK. IRON, NOT MINIMUM 6" 2) DID NOT CALL FOR ROCKED CHASE INSPECTION 3) WANT TO MEET WHITH CONTR. ON JOB |