Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2004 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :*/ 1) SOIL WTR TEST IS OK. 2) OVERHEAD WTR DISTRIBUTION IS OK. 3) GAS PRESSURE TEST IS OK. | |
| 05/05/2004 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ DOOR WAS LOCKED. |
|
| 05/04/2004 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) MUST VERIFY MARKINGS ON COPPER 2) MUST PROVIDE WATER TEST ON NEW WASTE AND VENT SYSTEM 3) MUST PROVIDE CLEANOUT FOR FLOOR SINK 4) CANNOT RUN A 2" TRAP ARM FOR WET VENT ON A 2" RISER BARREL MUST BE 1 PIPE SIZE LARGER 5) MUST USE STEEL UNISTRUT CLAMP FOR GAS LINE |
|
| 04/30/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |