Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 11/18/2003 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000* |
| 11/17/2003 |
ELECTRIC - CABLE DROP |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250.8 2) PLEASE CLEAN SURFACE UNDER LUGS 250.12 3) BONDING JUMPER TO BE SIZED PER 250.66 (TABLE) |
| 11/12/2003 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0999* 1) NEED TO INSTALL A JUMPER FROM UFER COMING INTO GUTTER TO NEUTRAL BUS. 2) NEED TO HAVE 2ND ADDRESS ON PERMIT BEFORE i CAN CLEAR IT TO TEP. |