Permit: T03CM03216


Addresses:

5821 E NORTH ST

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
11/18/2003 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*
11/17/2003 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection 0000*/ 1) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250.8 2) PLEASE CLEAN SURFACE UNDER LUGS 250.12 3) BONDING JUMPER TO BE SIZED PER 250.66 (TABLE)
11/12/2003 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0999* 1) NEED TO INSTALL A JUMPER FROM UFER COMING INTO GUTTER TO NEUTRAL BUS. 2) NEED TO HAVE 2ND ADDRESS ON PERMIT BEFORE i CAN CLEAR IT TO TEP.