Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ABOVE CEILING
Permit Number - T03CM03192
Inspection Description - PLUMBING - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/30/2004 | PLUMBING - ABOVE CEILING | Approved | IVRS - Inspection :*/CORRECTION MADE, REVISED CITY APP. PLAN ON SITE | |
11/24/2004 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/H2O PIPING WATER TEST OK. CLOSET FLANGES OK. WASTE & VENT THRU ROOF WATER TEST OK. 15 PSI AIR TEST ON GAS PIPING PER PLAN OK. 1)PROVIDE DIELECTRIC ON H2O SUPPLY 2)PROVIDE HANGERS & SUPPORTS AT 4' INTERVALS ON PLASTIC PIPING ON HORIZONTAL 3)PROVIDE ADDITIONAL HANGERS FOR 1/2 HAR? PIPING |