Permit: T03CM03190

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
10/15/2003 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
10/13/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) M/C CABLE TO BE ATTACHED AT BOTH ENDS 300.11 2) SUPPORT CUT IN BOXES TO GRID AND WITH A SUPPORT WIRE 3) FILL UNUSED OPENINGS IN BOXES 4) OK TO TILE EXCEPT AS NOTED