Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/31/2004 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 03/30/2004 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) DOES NOT INCLUDE TRUSS CALC'S |
| 03/29/2004 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 03/29/2004 |
FRAMING |
|
Denied |
1) PROVIDE MATCHING TRUSS CALC'S 2) SUPPORT WASTE IN L.R. 3) INSULATE JUNCTION AT DUCTS 4) SEAL 5) PROTECT ELECTRICAL AT SHARP EDGES 6) INSTALL 220V TO FURNACE ROOMS 7) 1/4" SLOPE AT TRAP ARMS 8) NAIL PLATE WASTE IN HALL BATH 9) FIRE STOP WATER HEATER STAND IN GARAGE 10) INSTALL HEARTH SAFETY STRIP |