Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 06/03/2004 |
FRAMING |
|
Approved |
IVRS - Inspection :* |
| 05/12/2004 |
FRAMING |
|
Partial Approval |
IVRS - Inspection :*/ 1) NEED COPY OF COUNTY RECORDERS DEED SHOWING 3' ACCESS EASEMENT WEST SIDE OF P/L 2) HAVE PLAN CHANGED RE: ASBUILT GARAGE FLOOR JOISTS 3) REDO WATER HEATER FLUE PIPE 4) CUT 1" AWAY FROM FIREPLACE FLUE |
| 04/14/2004 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) NEED DETAIL FIREWALL NON CONTINUATION AT FLOOR AND CEILING AT PROPERTY LINES 2) PLAN CALLS FOR TJI GARAGE AT 12" CENTER SPCING 3) CANNOT HAVE CONDENSATES, T & P LINE GAS OR ELECTRIC ON WEST WALL WHICH IS ON ADJOINING PROPERTY 4) HAVE REVISED PLAN SUBMITTED AND APPROVED REGARDING RELOCATE OF WASHER, DRYER AND WATER HEATER 5) COMPLETE OR CORRECT ITEMS 1, 2, 3, 4, 10 AND 12 ABOVE ALSO 6) STOPPED INSPECTION 7) COMPLETE AND RECALL |
| 04/12/2004 |
FRAMING |
|
Denied |
IVRS - Inspection 0950*/ 1) OPENINGS NOT ALLOWED IN 1 HOUR FIREWALL, COMBUSTION AIR CONDENSATES AND T & P LINE 2) GAS AND ELECTRIC CANNOT BE ON ADJOINING PROPERTY 3) WATER HEATER NOT LOCATED PER PLAN 4) LAUNDRY ROOM NOT LOCATED PER PLAN 5) LAG BOLTS MISSING LEDGER 4/S4 6) 3/S5 NOT COMPLIED WITH AT ENTRY-REQUIRE 3-2 X HEADER 7) STOPS TO NORTH ROOM RISE EXCEEDS 7 3/4" (KITCHEN) 8) ANCHOR BOLTS LOOSE THROUGHOUT 9) PLUMBING LEAK FROM TUB 10) FIRE STOP ALL 2ND FLOOR PENETRATIONS 11) BATHROOM ADDED 1ST FLOOR 12) ELECTRIC OUTLET NOT ALLOWED UNDER BAR/COUNTER TOP WITH OVER HANG GREATER THAN 6" 13) STOPPED INSPECTION TO MANY ITEMS |
| 03/15/2004 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |