Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2010 | MECHANICAL - FINAL | Partial Approval | ||
| 01/04/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) A/C UNITS ARE OK 2) EXHAUST FAN FOR KITCHEN IS NOT TYPE I 3) FAN CURB IS TO SHORT 4) FAN MUST DISCHARGE MINIMUM 40" ABOVE ROOF 5) CANNOT CONFIRM 16 GA. WELDED DUCT 6) INTERLOCK MAKE UP AIR WITH EXHAUST FAN 7) REMOVE GAS LINE FROM INSIDE THE HOOD AND SEAL HOLE INT OP HOOD 8) RELOCATE GAS LINE OUTSIDE OF HOOD 9) SCHEDULE AN INSPECTION WHEN FAN IS REMOVED 10) NEED TO SEE INSIDE GREASE DUCT 11) PROVIDE A HINGE KIT AND GASKET FOR NEW FAN |