Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
08/04/2010 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) CHECKED WELDS ON GREASE DUCT
2) OK FOR BOTH LAYERS OF FIRE WRAP
3) THE DUCT TRANSITION ABOVE HOOD WILL HAVE TO BE REPLACED-DOES NOT MEET TYPE I REQUIREMENTS
4) PROVIDE APPROVED DRAWINGS FOR MAKE UP AIR SYSTEM
5) 10,000 CGFM MAKE UP AIR CAN CAUSE A TEMPERATURE PROBLEM IN KITCHEN
01/06/2010 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) DISCUSSED TYPE I ISSUES AND REPAIRS