Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 09/26/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 09/25/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) SECURE HD'S SOUTH WALL 2) PLUMBERS TAPE NOT AN APPROVED HANGER 3) DOUBLE TOP PLATE REQUIRED UNDER FLOOR TRUSS AT STAIRS 4) MECH BLOCKING MISSING 2ND FLOOR 5) ATTIC ACCESS NOT PERMITTED IN BEDROOMS 6) MESH INCOMPLETE 7) STOPPED INSPECTION, TOO MANY ITEMS |
| 09/24/2003 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) NOT READY FOR INSPECTION, WORK IN PROGRESS |