Permit: T03CM03132

Parcel: 137314380

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
10/08/2003 FRAMING Approved IVRS - Inspection 0000*
10/07/2003 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) 110V CONDUCTOR DAMAGED BY STAPLE
10/02/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) 220V AND 110V CABLES DAMAGED BY STAPLE AT PANEL-REPLACE BOTH 2) NAIL PROTECT ALL WIRES WITHIN 1 1/4" OF STUD NAIL SURFACE 3) FURNACE "B" VENT WITHIN 1" OF COMBUSTIBLE MATERIAL 4) BEDROOM OUTLET WIRED DAMAGED BY LATH STAPLE-REPLACE 5) HEADERS MUST BEAR ON TRIMMERS 6) SEAL ALL VAPOR BARRIER PENETRATIONS 7) FHA STRAPS REQUIRE 6/16D NAILS EACH SIDE 8) RED HEAD ANCHORS LOOSE 9) EDGE NAILING OF WIRE NOT ALLOWED