Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T03CM03119
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2003 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
| 08/11/2003 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/IMC 307.2.3 / #2 NEED SEPERATE OVERFLOW LINE TERMINATING TO A CONSPICUOUS POINT OF DISPOSAL TO ALERT OCCUPANTS THAT THE PRIMARY DRAIN IS BLOCKED. NEED TO SEPERATE THE LINES. | |
| 07/29/2003 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ 1) ELECTRIC HIGH VOLTAGE TO AIR HANDLER ? 230 VOLT OR 115 2) IMC-307.2.3 AUX. SECONDARY PAND AND DRAIN ? 3) RE-LOCATE SUPPPLY REGISTER IN GRID, LOCATED IN FRONT OF AIR HANDLER. NEED CLEARANCES IN FRONT SIDE OF ? FOR SERVICE |