Permit: T03CM03119

Parcel: 113070470


Addresses:

2925 N CAMPBELL AV


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T03CM03119

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/29/2003 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
07/21/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*/ 1) THE ABOVE CEILING CONNECTION OF EQUIPMENT IS COMPLETE. 2) "TROFFER" LAY-IN FLOURESENT FIXTURES ARE NOT SUPPORTED PROPERLY PER PLAN SHT. A1.1. SEISMIC WIRES AND GRID TO FIXTURE SCREWS OR CLIPS MUST BE INSTALLED. 3) DISCONNECTS FOR A/C AIR HANDLER AND FOR WATER HEATER ARE NOT INSTALLED. COMPLETE AND RECALL.
07/07/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
07/02/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*