Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 07/29/2003 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 07/21/2003 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245*/ 1) THE ABOVE CEILING CONNECTION OF EQUIPMENT IS COMPLETE. 2) "TROFFER" LAY-IN FLOURESENT FIXTURES ARE NOT SUPPORTED PROPERLY PER PLAN SHT. A1.1. SEISMIC WIRES AND GRID TO FIXTURE SCREWS OR CLIPS MUST BE INSTALLED. 3) DISCONNECTS FOR A/C AIR HANDLER AND FOR WATER HEATER ARE NOT INSTALLED. COMPLETE AND RECALL. |
| 07/07/2003 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* |
| 07/02/2003 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999* |