Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/21/2003 |
ELECTRIC - INTERMEDIATE |
|
Approved |
|
| 07/07/2003 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK WALLS SUBJECT TO LETTER FOR #5 PREVIOUS INSPEC. SHELL PLANS CALL FOR ELEC TO #7,8,& 10 |
| 07/02/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) PROTECT CABLES AT STUDS 2) PLEASE VERIFY USE OF M/C CABLE 3) TIGHTEN LOOSE M/C FITTINGS 4) FILL UNUSED OPENINGS IN BOXES 5) WHERE ARE OUTLETS THAT PLANS CALL FOR 6) SUPPORT M/C CABLE WITHIN 12" OF BOXES 7) PLEASE REVISE PLANS FOR BATH ROOMS, THEY HAVE BEEN DONE AS NEW CONSTRUCTION 8) PLEASE SHOW NEW WATER HEATER ON PLANS 9) REPAIR BROKEN M/C SHEATH 10) SERVICE IS NEW-WHERE IS ONE-LINE DIAGRAM |