Permit: T03CM03118

Parcel: 133230910

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/13/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
08/11/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) GROUND ALL METAL JUCTION BOXES 2) USE APPROVED SPLICE CONNECTORS FOR GROUNDS 3) NEUTRALS NOT TO PASS THROUGH DEVICE 4) WE HAVE MORE NEW CIRCUITS THAN ON PLANS 5) NEUTRALS NOT TO BE MORE THAN ONE PER TERMINAL 6) NEED A LETTER FROM ARCHITECT AUTHORIZING USE OF NM CABLE AND M/C CABLE-PLANS CALL FOR RACEWAY'S 7) LIGHT FIXTURES NOT RELOCATED