Permit: T03CM03116

Parcel: 134190830


Addresses:

75 S MONTEGO DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/13/2005 MECHANICAL - FINAL Approved IVRS - Inspection :* OK FOR FINAL C OF O
01/11/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 3/8 GAS FLEX NOT ADEQUATE FOR 7.;5 TON A/C UNIT PLASTIC CONDUIT PENETRATING THE CABINETS OF A/C UNITS MUST BE PROTECTED WITH A BUSHING. PROVIDE DUCT SMOKE DETECTOR IN 7.5 TON UNIT RECALL FOR INSPECTION.
01/10/2005 MECHANICAL - FINAL Cancelled IVRS - Ri canceled
12/27/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*/OK FOR TEMP C/O