Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03CM03116
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/13/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* OK FOR FINAL C OF O | |
| 01/11/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 3/8 GAS FLEX NOT ADEQUATE FOR 7.;5 TON A/C UNIT PLASTIC CONDUIT PENETRATING THE CABINETS OF A/C UNITS MUST BE PROTECTED WITH A BUSHING. PROVIDE DUCT SMOKE DETECTOR IN 7.5 TON UNIT RECALL FOR INSPECTION. |
|
| 01/10/2005 | MECHANICAL - FINAL | Cancelled | IVRS - Ri canceled | |
| 12/27/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :*/OK FOR TEMP C/O |