Inspection History Details
Inspection Status: Approved
Inspection History: STEM WALL/RETAINING WALL
Permit Number - T03CM03116
Inspection Description - STEM WALL/RETAINING WALL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2004 | STEM WALL/RETAINING WALL | Approved | IVRS - Inspection :* | |
| 06/30/2004 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection :* | |
| 06/08/2004 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection :* | |
| 06/01/2004 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection :*E, S & N | |
| 05/25/2004 | STEM WALL/RETAINING WALL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) STEM VERTS REQUIRE 2" CONCRETE COVERAGE TO EARTH, 1 1/2" TO WEATHER AND 3/4" TO INTERIOR MINIMUM 2) GET AN RFI FOR THE MISPLACED VERTICALS-DETAILING HOW TO REPAIR 3) PLEASE SET A LARGER PLAN GUB |