Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T03CM03109
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/06/2003 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
10/30/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ 1) FINISH WIRE SUPPORTS TO CANS 2) BOXES TO BE SUPPORTED 3) CHECK CONDUCTOR FILL 4) PREVENT DIELECTRIC CONTACT 5) OK TO TILE EXCEPT AS NOTED | |
10/17/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ 1) OK TO USE 2 A/C UNITS | |
10/14/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ 1) A/C UNITS DISC. SWITCHES MUST HAVE 30" HORIZONTAL AND 36" IN FRONT DEDICATED WORKING AREA. PER 110-26 NEC | |
10/10/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ 1) NOTES: OK SOFFITS |