Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/06/2003 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 10/30/2003 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) FINISH WIRE SUPPORTS TO CANS 2) BOXES TO BE SUPPORTED 3) CHECK CONDUCTOR FILL 4) PREVENT DIELECTRIC CONTACT 5) OK TO TILE EXCEPT AS NOTED |
| 10/17/2003 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK TO USE 2 A/C UNITS |
| 10/14/2003 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) A/C UNITS DISC. SWITCHES MUST HAVE 30" HORIZONTAL AND 36" IN FRONT DEDICATED WORKING AREA. PER 110-26 NEC |
| 10/10/2003 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) NOTES: OK SOFFITS |