Permit: T03CM03109


Addresses:

5955 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T03CM03109

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
11/06/2003 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
10/30/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) FINISH WIRE SUPPORTS TO CANS 2) BOXES TO BE SUPPORTED 3) CHECK CONDUCTOR FILL 4) PREVENT DIELECTRIC CONTACT 5) OK TO TILE EXCEPT AS NOTED
10/17/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) OK TO USE 2 A/C UNITS
10/14/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) A/C UNITS DISC. SWITCHES MUST HAVE 30" HORIZONTAL AND 36" IN FRONT DEDICATED WORKING AREA. PER 110-26 NEC
10/10/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) NOTES: OK SOFFITS