Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03CM03104

Parcel: 12501022A


Addresses:

2555 E 1ST ST #103

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/19/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
11/18/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) SECURE NM CABLES TO PANEL 2) FINISH #1, 3 AND 12 3) RECIEVED LETTER FOR NM CABLE 4) OK TEMP C OF O
11/17/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) SUPPORT WIRES ARE NEEDED FOR ALL NEW AND RELOCATED FIXTURES ALSO ATTACH TO GRID 410.16 TRAC OF 2 X4'S 2) BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AND APPROVED EXTENDER RING 370.20-METAL NOT APPROVED 3) SEAL WALK IN BOX ELECTRIC IN CONDUIT AT ENTRANCE TO BOX 300.5 (9) 4) TIGHTEN LOOSE FITTINGS AND SUPPORT SEAL TITE CONDUIT ALL LOCATIONS 5) CIRCUIT DIRECTORY TO BE REVISED FOR NEW CIRCUITS 6) ROOF UNIT NEED DISCONNECTING MEANS 7) EMERGENCY LIGHTING AND EXIT TO BE ON CIRCUIT IN AREA ASSOCIATED WITH 700.12 8) TIGHTEN ROOF FITTINGS TO DISCONNECT 9) WHERE IS GROUND CONDUCTOR TO UNIT ? 10) NM CABLE IS NOT ALLOWED IN EXHAUST HOOD ON ROOF 300.22 11) WHERE IS LETTER AS ASKED ON PREVIOUS INSPECTION 12) 370.43 CONDUCTORS AND SCREWS M/C LETTER