Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 04/19/2004 |
MECHANICAL - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000*/ 1) OVER FRONT OFFICE |
| 02/06/2004 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ OVERFLOW SENSORS, AIR HANDLERS OVER FRONT OFFICE AREA, OK. JOB PROGRESSING. |
| 02/03/2004 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) ISOLATE ALL COPPER, ESPECIALLY REFRIGERANT LINE COPPER, FROM STEEL STRAPS. 2) A/C 1 & 2, AUX OVERFLOW CONDENSATE LINE, MUST RUN TO CONSPICUOUS LOCATION SO IT CAN BE DETERMINED PRIMARY IS BLOCKED. 3) AIR HANDLER - REAR NORTHEND, REFRIG LINES ARE BLOCKING CLEAR ACCESS. THREADED ROD TO SUPPORT UNI-STRUT IS BLOCKING BLOWER ACCESS? |