Permit: T03CM03075

Parcel: 14024058G


Addresses:

1075 E WIEDING RD

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
04/19/2004 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*/ 1) OVER FRONT OFFICE
02/06/2004 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ OVERFLOW SENSORS, AIR HANDLERS OVER FRONT OFFICE AREA, OK. JOB PROGRESSING.
02/03/2004 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) ISOLATE ALL COPPER, ESPECIALLY REFRIGERANT LINE COPPER, FROM STEEL STRAPS. 2) A/C 1 & 2, AUX OVERFLOW CONDENSATE LINE, MUST RUN TO CONSPICUOUS LOCATION SO IT CAN BE DETERMINED PRIMARY IS BLOCKED. 3) AIR HANDLER - REAR NORTHEND, REFRIG LINES ARE BLOCKING CLEAR ACCESS. THREADED ROD TO SUPPORT UNI-STRUT IS BLOCKING BLOWER ACCESS?