Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 02/25/2004 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*/ 1) WASTE AND VENT SYSTEM IS OK 2) OVERHEAD WATER DISTRIBUTION IS OK 3) OK FOR DRYWALL 4) NOTE: MUST SEE INSTALLATION OF CLOSET RINGS PRIOR TO SETTING TRIM |
| 02/20/2004 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) H.C. FLUSH VALVE HIEGHT MAX IS 44". 2) URINAL REQUIRES A 2" DRAIN. 3) RE-TEST SYSTEM. |
| 02/18/2004 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 02/17/2004 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) OVERHEAD WTR DISTRIBUTION IS OK. 2) OK FOR DRYWALL. 3) THIS INSPECTION IS FOR ROOMS 205B, 206B, 207B, 212B, 213B, 214B, 215B, 305B, 306B, 307B, 308B, 312B, 313B, 314B, AND 315B. |
| 01/13/2004 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |