Permit: T03CM03075

Parcel: 14024058G


Addresses:

1075 E WIEDING RD

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
02/25/2004 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*/ 1) WASTE AND VENT SYSTEM IS OK 2) OVERHEAD WATER DISTRIBUTION IS OK 3) OK FOR DRYWALL 4) NOTE: MUST SEE INSTALLATION OF CLOSET RINGS PRIOR TO SETTING TRIM
02/20/2004 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) H.C. FLUSH VALVE HIEGHT MAX IS 44". 2) URINAL REQUIRES A 2" DRAIN. 3) RE-TEST SYSTEM.
02/18/2004 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
02/17/2004 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*/ 1) OVERHEAD WTR DISTRIBUTION IS OK. 2) OK FOR DRYWALL. 3) THIS INSPECTION IS FOR ROOMS 205B, 206B, 207B, 212B, 213B, 214B, 215B, 305B, 306B, 307B, 308B, 312B, 313B, 314B, AND 315B.
01/13/2004 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OVERHEAD WATER DISTRIBUTION IS OK FOR H.B. SUPPLYS. 2) OK TO DRYWALL THESE WALLS ONLY. 3) 2" C.W. SUPPLY FROM BLDG TO P.L. OK TO BACKFILL TRENCH.