Permit: T03CM03075

Parcel: 14024058G


Addresses:

1075 E WIEDING RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/13/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
04/02/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ OK WALLS SOUTH MAIN OFFICES.
03/25/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) BOND NEUTRALS IN SERVICE DISCONNECTS, PER 250-24B. BOND SIZE PER 250-66. 2) INSTALL WATER AND GAS PIPE BONDING. 3) SIZE EQUIP GROUNDS PER NEC FOR PARALLEL RUNS 250-104. 4) LABEL DISCONNECT SWITCHES. 5) BOND X-FORMER PER NEC REQUIREMENTS, ARTICLE 250 SEPERATLY DERIVED SYSTEMS.
02/11/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
01/29/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ OK WALLS FOR OFFICES - DUE NORTH OF TELEPHONE ROOM.