Permit: T03CM03068

Parcel: 114469370

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
08/13/2003 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
08/12/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*/ 1) M/C CABLE TO BE INDEPENDENTLY SUPPORTED 300.11 2) EXIT SIGN NEED SUPPORT WIRE 3) WHAT IS COIL OF M/C CABLE ON TOP OF LIGHT FIXTURE ? 4) SUPPORT M/C CABLE AS PER CODE 12" FROM BOX OR FITTING 5) PANEL COVER TO BE FULLY ACCESSIBLE 6) PROVIDE REJECTION PW AT SERVICE 7) BOXES WITH MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 370.20 METAL NOT APPROVED