Inspection History Details
Inspection Status: Not Applicable
Inspection History: STUCCO MESH
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2008 | STUCCO MESH | Not Applicable | IVRS - Inspection :* | |
| 10/02/2006 | STUCCO MESH | Not ready for Inspection | IVRS - Inspection :* 1) STUCCO MESH CHANGED TO BRICK VENEER IN FAMILY ROOM KEY NOTE 17 2) SOLAR PANEL WILL BE OMITTED FROM PLAN 3) NAIL PROTECT HOME RUNS PANEL B 4) EXTRA CAN LIGHTING ADDED THROUGHOUT NOT ON PLANS 5) COMPLETE REGISTER BOOT BEDROOM 4 6) SECURE ROMEX 8" FROM BOXES THROUGHOUT 7) SECURE 4 GANG BOXES MASTER BEDROOM 8) BLOCK REGISTER BOOTS 3 SIDES BATH 2 9) GROUND ALL METAL BOXES 10) PROVIDE GAS & COPPER BONDS 11) FIREBLOCK AT NAILER FAMILY ROOM SOUTH WALL 13) BLOCK PLENIUM KITCHE 14) SUBMIT ALL AS BUILTS PRIOR TO INSPECTION OR BUILD TO PLAN |
|
| 09/22/2006 | STUCCO MESH | Denied | IVRS - Inspection : See detailed listing on site.| 999* |