Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T03CM03022
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/29/2003 | FRAMING | Approved | IVRS - Inspection 0000* | |
08/26/2003 | FRAMING | Denied | IVRS - Inspection 0935*/ 1) EPOXY BOLT SPECIAL INSPECTOR NOT AUTHORIZED BY CITY OF TUCSON. INSPECTION REPORT TAKEN FOR REVIEW BY BLDG OFFICIAL 2) THIRD FAILURE, REFEE | |
08/25/2003 | FRAMING | Denied | IVRS - Inspection 0940*/ 1) PROVIDE PROOF THAT SPECIAL INSPECTOR FOR EPOXY IS CERTIFIED BY CITY OF TUCSON 2) ANCHOR BOLTS REEQUIRED AT 48" ON CENTER B/R 3) LEAK DWV M/TUB 4) NAIL PROTECT WIRES WITHIN 1 1/4" OF WALL SURFACES | |
08/22/2003 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) EPOXY BOLT SPECIAL INSPECTOR IS NOT CERTIFIED BY CITY OF TUCSON HAVE RE-CERTIFICATION PULL TEST APPLIED 2) NON-BEARING WALLS REQUIRE 1/2" CLEARANCE TO SCISSOR TRUSSES 3) NO DWV WATER TEST ON PLUMBING 4) BACK GROUT TUB PENETRATION 5) ANCHOR BOLTS REQUIRED AT 32" ON CENTER 6) NAIL PROTECT WIRES WITHIN 1 1/4" OF WALL SURFACE |