Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/20/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 07/13/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) INSTALL DUCT SMOKE DETECTORS AS PER PLANS 2) PROVIDE FRESH AIR INTAKES AS PER PLANS 3) 5 TON UNIT OVERFUSED-35 AMP IS MAX |
|
| 07/06/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* |