Permit: T03CM02992

Parcel: 130031420


Addresses:

1517 S TUCSON BL

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
02/09/2004 FRAMING Approved IVRS - Inspection 0000*
02/06/2004 FRAMING Denied IVRS - Inspection 0999*/ 1) PROVIDE WATER TEST ON PLUMBING TOP OUT 2) PROTECT ALL PLUMBING AND ELECTRIC. CLOSER THAN 1 1/4" FROM FACE OF STUDS RAFTERS 3) SECURE ALL WIRES 8" FROM J-BOXES 4) FIRE BLOCK MISSING AT BATHROOM
02/04/2004 FRAMING Denied IVRS - Inspection 0999*/ 1) PLAN CALLS FOR 1" GAS LINE TO FURNACE/WATER HEATER 3/4" INSTALLED 2) REVISE SITE PLAN FROM 10/03/03 INSPECTION 3) GAS LINE NOT BONDED. REMOVE PLASTIC 4) MAXIMUM ALLOWED SPACE BETWEEN OUTLETS 12' 5) ELECTRIC OUTLET REQUIRED WITHIN 6' OF DOOR 6) SECURE WIRES WITHIN 8" OF BOXES 7) S/D 36" FROM AIR ? 8) MAKE UP ALL GROUNDS AND SECURE WITH MECHANICAL FASTENERS 9) PROVIDE DWV WATER TEST 10) T & P LINE MUST EXHAUST OUTSIDE 6" AND 18 ABOVE GROUND